# **X-PoE BASIC TROUBLESHOOTING — LOADS NOT TURNING ON** - GUIDE

## About This Guide

This guide provides a quick verification method to identify the cause when a load connected to an X-PoE system is not operating. The goal is to determine whether the issue originates from a cable issue, a PD/fixture connection issue, or an X-PoE switch configuration issue.

## Possible Issue Areas

### Cable Issue

- Faulty or damaged CAT6 cable
- Improper cable installation

### PD / Fixture Connection Issue

- Poor connection between the PD and the LED fixture
- LED module failure

### X-PoE Switch Issue

- Switch configuration preventing load activation
- Port configuration or hardware issue

## Assumptions

Before beginning troubleshooting:

- Switch firmware/software is current
- X-PoE switch is configured for automatic load discovery and activation (default configuration)
- CAT6 cable has previously been tested and verified functional
- The technician knows the switch, port, and channel associated with the affected load

## Terms

| Term | Definition |
| --- | --- |
| **Affected Fixture** | The light or DC outlet being investigated. It is expected to be ON but currently is not. |
| **X-PoE Switch** | A DC lighting control network switch with integrated LED drivers (e.g., XS-108H). |
| **Port** | A physical network port on the X-PoE switch that provides power and communication. |
| **Channel** | Individual power output on a port. Each port typically provides two independent channels (CH1 and CH2). |
| **PD** | Power Distribution Module — device used to connect a fixture to the CAT6 cable. |
| **Aggregated Load** | Two fixtures connected together and powered from both channels of a single port instead of two independent fixtures. |

## Required Tools

1. **Test Load** — known-good load that auto-discovers and turns on
2. **Troubleshooting Module** — pass-through PD with no signature resistors
3. **DMM** — Digital Multimeter
4. **AMM** — Analog Multimeter (useful for observing scanning signals)

## Troubleshooting Overview

Start troubleshooting in the telecommunications room to avoid ladder work whenever possible.

The Troubleshooting Module helps determine whether the issue lies toward the switch or toward the fixture.

### Interpretation Guide

| Observation | Likely Cause |
| --- | --- |
| No scanning signal | Issue toward the X-PoE switch |
| No signature resistance | Issue toward the affected fixture |
| Scanning signal + signature resistance | Continue testing with test load |

### Test Load Results

| Result | Likely Cause |
| --- | --- |
| Test load turns on | Issue likely between PD and LEDs, or inside the LED fixture |
| Test load does not turn on | X-PoE switch may not be configured to enable the load |

Move from the network closet toward the affected fixture using the troubleshooting module to isolate the failure point.

## Procedure

Begin troubleshooting at the X-PoE switch in the telecommunications room. Each step determines whether the fault lies toward the switch or toward the load.

### Step 1 — Identify the Port

Locate the X-PoE switch and port supplying the affected fixture. Verify:

- Correct cable is connected
- Port status indicator

### Port Status Indicators

| LED Color | Meaning |
| --- | --- |
| Red | Switch detected an error (possible cable issue) |
| White (solid/flashing) | Port not providing power (possible cable issue) |
| Green (solid/flashing) | Port providing power (possible fixture issue) |
| Orange | Connected to IEEE load (e.g., DCO-65) |
| No LED | Verify X-PoE switch power |

### Step 2 — Test Cable Toward Fixture

Disconnect the CAT6 cable from the switch and connect it to the Troubleshooting Module. Use a Digital Multimeter to measure signature resistance.

### Channel 1 Test

Measure: CH1 + → CH1 -

| Result | Meaning |
| --- | --- |
| Short | Cable fault |
| Open | Load not connected or cable fault |

Expected resistance values:

| Device | Resistance |
| --- | --- |
| LED Fixture | 7 kΩ – 25 kΩ |
| DCO-65 / IEEE PoE | ~25 kΩ |
| DCO-100 | 45 kΩ – 50 kΩ |

### Channel 2 Test

Measure: CH2 + → CH2 -

Interpret results the same as Channel 1.

### Step 3 — Test Cable Toward Switch

Connect CAT6 cable from the X-PoE switch to the Troubleshooting Module. Use an Analog Multimeter to measure voltage.

### Channel 1

Measure: CH1 + → CH1 -

| Result | Meaning |
| --- | --- |
| No voltage | Cable or switch issue |
| Voltage above 24V | Switch verified load and enabled power |
| Pulsing ~10V once/sec | Normal scanning behavior |

### Channel 2

Measure: CH2 + → CH2 -

Interpret results the same as Channel 1.

### Step 4 — Verify Fixture Operation

Plug the test load directly into the X-PoE switch and wait up to 30 seconds.

> **Expected Result**
> The test load turns on. This confirms the X-PoE switch is operational and port configuration is correct.
>
If cable tests also pass, the issue likely exists inside the LED fixture or PD connection.

## Key Takeaway

Start troubleshooting at the network closet and work outward. Using the troubleshooting module quickly determines whether the issue lies toward the switch or toward the fixture, minimizing ladder work and reducing troubleshooting time.

## Related Information

### Technical Support

Questions about a load that will not turn on can be sent to [support@luum.io](mailto:support@luum.io). Include the switch, port, channel, LED color, and the resistance or voltage you measured.

### Document Feedback

While we have taken great care to ensure the accuracy and completeness of this document, we welcome your feedback and suggestions. If you notice any errors or omissions, or feel a topic could benefit from further explanation, please email your feedback to [support@luum.io](mailto:support@luum.io).

### Revision History

| Date | Revision | Notes |
| --- | --- | --- |
| 11/3/2026 | A | Converted to the current guide format. |

### Disclaimer

All rights, title, and interest in and to this guide, including without limitation all copyright, trademark, patent, trade secret, and other proprietary rights, belong solely and exclusively to Luum.io and/or its licensors. This guide is provided solely for the purpose of troubleshooting an X-PoE load that does not turn on, and no license or other rights are granted or implied hereby. No part of this guide may be reproduced, distributed, or transmitted in any form or by any means, including photocopying, recording, or other electronic or mechanical methods, without the prior written permission of Luum.io. The contents of this guide are subject to change without notice. The information contained herein is provided on an 'as is' basis and is for informational purposes only. Luum.io makes no warranty, express or implied, as to the accuracy, completeness, or usefulness of this information, nor does it assume any legal liability or responsibility for the consequences of any errors or omissions therein. The names of actual companies and products mentioned herein may be the trademarks of their respective owners.

---

_©2026 Luum.io. All rights reserved._