> For the complete documentation index, see [llms.txt](https://luum.io/llms.txt).
> Canonical page: [ALC](https://luum.io/docs/amatis/data-sheets/alc).

LUUM.IO

# **Advanced Load Controller (ALC)** - PRODUCT SPECIFICATION

_Power and fixture control_

![Advanced Load Controller (ALC)](https://luum.io/guides/assets/alc/ALC%20Hero.png)

## Product Overview

The Luum Advanced Load Controller (ALC) is a lighting controller and power control device used to manage entire branches of lighting loads, individual fixtures, or plug loads.

The ALC communicates wirelessly via the embedded 6LoWireless protocol.

The ALC can receive occupancy, vacancy, daylight, temperature, and humidity data from an optional connected sensor and transmit that data across the network.

The ALC is able to measure and report power consumption to help track energy usage and detect failed drivers or lamps.

## Configurations

| SKU | Description |
| --- | --- |
| XWS-ALC-C | Load controller with relay, 0-10V dimming, wireless control and onboard power metering. |

## Features

| Feature | Description |
| --- | --- |
| **Fixture control functionality** | • Controls individual lights or branch circuits up to 20AMP<br>• Plug load (receptacle) control can disable receptacles when rooms are vacant to save energy<br>• Self-contained relay switches line voltage loads with 0-10V output for dimming<br>• RJ12 input for MLTH2 Sensor detecting motion, light, temperature and humidity<br>• Onboard power metering |
| **Simple installation** | • Quickly installs using a 1/2'' knock-out on a junction box or fixture<br>• LEDs indicate power and network connection status |
| **Simple startup** | • Remotely configurable / upgradeable<br>• Luum app commissions devices on the mesh network<br>• Unique IPv6 address<br>• Real-time data uploaded to the Energy Dashboard |
| **Energy Code** | • Complies with ASHRAE 90.1-2016 and CA Title 24 requirements |
| **Certifications** | • ETL Listed (cETLus) to UL 60730-1 |
| **Warranty** | • 5-year limited warranty with uninterrupted connection of the Luum Border Router device from a network |

### ALC Wiring Diagram

![ALC Wiring Diagram](https://luum.io/guides/assets/alc/ALC%20Feature.png)

| Item | Description |
| --- | --- |
| 1 | BLACK: Line (100-347 VAC) |
| 2 | WHITE: Neutral |
| 3 | RED: Relay COM/NC |
| 4 | RED: Relay COM/NC |
| 5 | PURPLE: 0-10V+<br>GRAY: 0-10V- |

## Specifications

| Category | Specification | Value |
| --- | --- | --- |
| **COMMUNICATION** | Wireless Transmit Range | Up to 200 feet line of sight to nearest mesh connected device |
|  | Communication Protocol | Embedded 6LoWireless |
|  | Encryption | AES 128-bit |
| **MECHANICAL** | Dimensions | 105 mm (127 mm with cap) x 64 mm x 32 mm (4.5 in (5 in with cap) x 2.5 in x 1.3 in) |
|  | Wire Colors | Black (L), White (N), Red (Switched), Violet (10V), Gray (0V) |
|  | Finish | White Matte |
|  | Enclosure | Type 2, Plenum Rated |
|  | External Outputs | On-board button for manual control • Push and hold to dim • Press to toggle on/off |
| **ELECTRICAL** | Input Voltage | 100-347VAC 50/60Hz |
|  | Low Voltage Output | Class 2, 150mA @ 16VDC |
|  | Dimming | 0-10V, 1-10V source or sink operation |
|  | Power Metering | Accurate to within 5% |
|  | Relay | 20A @ 120VAC<br>16A @ 277VAC<br>1/2HP @ 120/277VAC<br>7A @ 347VAC<br>Isolated Normally Open and Closed contacts |
| **ENVIRONMENT** | Installation Environment | Commercial, Indoor/Covered |
|  | Temperature Range | For 120V & 277V: -30 °C to +55 °C (-22 °F to 130 °F)<br>For 347V: -30 °C to +50 °C (-22 °F to 122 °F) |
| **GENERAL** | Standards / Ratings | FCC • ETL Listed (cETLus) to UL 60730-1 and UL 2043 |
|  | System Compliance Note | Device contributes to Luum system compliance with ASHRAE 90.1-2016 and CA Title 24 requirements |
|  | Warranty | 5-year limited warranty with continuous cloud connection |

---

_©2026 Luum. All rights reserved._